国产主播看片网站|一级全黄毛片免费不卡直接观看|无码人妻精品一区二区三区蜜桃91|日本加勒比不卡久久|91在线视频免费看|91日本高清在线观看|鲁一鲁亚洲天堂|五月桃花亚洲天堂|日韩天堂一区二区|久热这里只有精品69

Explosion-proof lightning protection box HD-D380/220C-XSF

Online Inquiry
Click Refresh Verification Code

Details

Crate-type explosion-proof power supply lightning protection box

Electric surge protector of low-voltage distribution system, which is in the form of a box, is explosion proof and designed according to IEC standard. It has invalidation detection indication, overflowing and overheating protection with powerful discharge capacity of lightning current. It's applicable to the protection of buildings' general supply system against lightning. It is very convenient to be maintained. It connects with the circuit in parallel and has no limit to the power of equipment fixed later.


Model

 

HD-D380(220)B-XSF60

 

HD-D380(220)C-XSF40

 

HD-D380(220)C-XSF20

 

HD-D380/220C-XSF

Nominal working voltage Un

 

380V/220V

 

380V/220V

 

380V/220V

 

380V/220V

Maximum continuous working voltage Uc

 

385V/275V

 

385V/275V

 

385V/275V

 

385V/275V

Nominal discharge currentIn8/20ms

30KA

 

20KA

 

10KA

 

20KA

Maximum discharging currentImax8/20ms

60KA

 

40KA

 

20KA

 

40KA

Voltagprotection level Up

2KV

1.6KV

 

1.2V

 

2.1KV

Prepositive overflowing protection

63A

 

32A

 

16A

 

32A

Overall dimension

 

260×180×85mm

Response time Ta

 

25ns

Operating temperature range Tup

 

-40℃至+70

Working order indication

Green light means normal working, red light is fault indication.

Section of minimum installed conductor

6m2 Multi-folded wire

Explosion proof function

Available

Protection grade

IP20

Sheathing material

Metal spraying

Mode of connection

Parallel connection

Protection mode

4+0/3+1/1+1/2+0


Ground the null line repeatedly when Long-distance overhead incoming lines enter buildings.

Plug the power phase line (L) and null line (Ninto corresponding connector of the electric surge protector and make sure it's firm and reliable. Connect the ground terminal of arrester with the ground lead of lightning protection well (recommended earth resistance 4Ω).

Suggested specification of the lead wire: no less than 6mm2, short and straight.


Home
Tel
Message
Contact